North Carolina Performance Enhanced Relocatable Classroom Project: An Evaluation of Design Changes to a Typical Relocatable Classroom

dc.contributor.advisorDr. Herbert M. Eckerlin, Committee Co-Chairen_US
dc.contributor.advisorDr. James W. Leach, Committee Chairen_US
dc.contributor.authorRaper, Garrett Matthewen_US
dc.date.accessioned2010-04-02T17:57:51Z
dc.date.available2010-04-02T17:57:51Z
dc.date.issued2005-04-27en_US
dc.degree.disciplineMechanical Engineeringen_US
dc.degree.levelthesisen_US
dc.degree.nameMSen_US
dc.descriptionNorth Carolina State University Theses Mechanical and Aerospace Engineering.
dc.description.abstractIn this study, the energy consumption of two relocatable classrooms located on the southern portion of the campus of Chapel Hill High School in Chapel Hill, NC is investigated. One classroom, the control, was specified and purchased by the Chapel Hill-Carrboro City School System. The other is a performance enhanced classroom designed by the Florida Solar Energy Center and purchased by the North Carolina Solar Center. Both classrooms are 24' by 40' modular structures, completely underpinned, and located adjacent to one another for a side by side comparison. The energy consumption and indoor conditions of each classroom are monitored by a data-logging system that also records outdoor conditions via a weather station. The performance enhanced classroom is equipped with a 3 ton, SEER 12 heat pump controlled by a Bard CS2000 unit, six skylights, increased insulation and envelope sealing, a demand control ventilation system with an energy recovery wheel, and a day lighting system controlled by occupancy sensors. The control classroom is equipped with a wall-mounted 10 kW electric furnace/air conditioning system. A programmable thermostat was also installed in the control classroom after two months of data was collected. A building model is prepared using the Energy-10 software package to estimate the impact the various design changes have on the energy consumption of each classroom.en_US
dc.formatThesis (M.S.)--North Carolina State University.
dc.identifier.otheretd-04272005-093554en_US
dc.identifier.urihttp://www.lib.ncsu.edu/resolver/1840.16/712
dc.rightsI hereby certify that, if appropriate, I have obtained and attached hereto a written permission statement from the owner(s) of each third party copyrighted matter to be included in my thesis, dissertation, or project report, allowing distribution as specified below. I certify that the version I submitted is the same as that approved by my advisory committee. I hereby grant to NC State University or its agents the non-exclusive license to archive and make accessible, under the conditions specified below, my thesis, dissertation, or project report in whole or in part in all forms of media, now or hereafter known. I retain all other ownership rights to the copyright of the thesis, dissertation or project report. I also retain the right to use in future works (such as articles or books) all or part of this thesis, dissertation, or project report.en_US
dc.subjectEnergy 10en_US
dc.subjectefficient constructionen_US
dc.subjectdaylightingen_US
dc.subjectbuilding modelingen_US
dc.subjectenergy efficienten_US
dc.subjectschool traileren_US
dc.subjectmodular classroomen_US
dc.titleNorth Carolina Performance Enhanced Relocatable Classroom Project: An Evaluation of Design Changes to a Typical Relocatable Classroomen_US
dcterms.abstractKeywords: Energy 10, efficient construction, daylighting, building modeling, energy efficient, school trailer, modular classroom.
dcterms.extentviii, 54 pages : illustrations (some color)

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
etd.pdf
Size:
696.45 KB
Format:
Adobe Portable Document Format

Collections